Configuring Voice Gateway Media Cards on cabinets or chassis 265
e. Configure IP Phone dedicated soft keys.
3. Configure IP Line data with OTM or Element Manager. See "Configuring
IP Line data with OTM 2.2" (page 268) and "Configuring IP Line data
with Element Manager" (page 269).
4. Transmit IP Line node configuration data from OTM or Element Manager
to the Voice Gateway Media Cards.
5. Upgrade the Voice Gateway Media Card software and IP Phone set
firmware.
6. Assemble and install IP Phones. Refer to IP Phone Fundamentals
(NN43001-368) for instr uctions on the installation of the IP Phone.
7. For a survivable system, verify IP Line operation in survival mode. Refer
to Procedure 59 "Verifying the operation of a VGMC in an IP Expansion
Cabinet or Chassis in survival mode" (page 319).
Configuring Voice Gateway Media Cards on cabinets or chassis
Use Procedure 50 "Configuring the ELAN network interface IP address for
the Small System active ELNK Ethernet interfac" (page 265) and Procedure
51 "Configuring the ELAN network interface IP address for the Small
System active ELNK Ethernet interfac" (page 266) to configure the Small
System’s Main Cabinet or Chassis and any Fiber or IP Expansion Cabinets
or Chassis.
Procedure 50
Configuring the ELAN network interface IP address for the Small System
active ELNK Ethernet interface on the Main Cabinet or Chassis, if not already
defined
Step Action
1
Go into LD 117.
2
Create host entries with IP address on the ELAN network interface.
Enter the following command:
NEW HOST <hostname> <IP_addr> <cab#>
where
<cab#> = 0, for the Main Cabinet or Chassis
3
Configure the ELAN Mask. Enter the following command:
CHG MASK <maskvalue> <cab#>
where
<maskvalue> = xxx.xxx.xxx
<cab#> = 0, for the Main Cabinet or Chassis
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310 01.04 Standard
Release 5.0 13 May 2008
Copyright © 2008, Nortel Networks
.