64 Bracing against earthquakes
You need a backboard that is large enough to hold all of the
components that you will install on the wall. To deter mine the
backboard size, refer to the wall plan that you developed using the
guidelines in Communication Server 1000M and Meridian 1 Small
System Planning and Engineering (NN43011-220). If you have not
developed a wall plan, please develop one now.
When you have determined the required backboard size, make sure
the measurements are within the limits listed in Table 15 "Backboard
size limits" (page 64).
Table 15
Backboard size limits
Backboard size
Minimum
0.6 m by 1.8 m (2 ft by 6 ft)
Maximum
1.2 m by 2.4 m (4 ft by 8 ft)
2 Determine fastener requirements.
You need the following information to determine fastener
requirements:
What fasteners you must use.
How deeply you must embed the fasteners into the wall.
The vertical distance between fasteners.
The horizontal distance between fasteners. For wood and metal
stud walls, determine this spacing by the spacing between wall
studs. Wall stud spacing must be within the range listed in Table
16 "Stud spacing" (page 64).
The required wall stud sizes for wood and metal stud walls.
Table 16
Stud spacing
Stud spacing
Minimum
0.4 m (16 in.)
Maximum
0.6 m (24 in.)
Table 17 "Hardware recommendations" (page 65) provides the
hardware recommendations for earthquake bracing the Small
System.
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310 01.04 Standard
Release 5.0 13 May 2008